electrical academy · lesson 3 · about 15 minutes

How long can a cable be?

A longer cable resists fault current more. If the fault current gets too small, the protection may not trip quickly. This lesson shows the idea with a worked example.

Learning material, not a design or safety instruction. Electrical work must be done by qualified people following the maker's instructions and local rules.

The idea

  • In a short circuit between a live conductor and neutral or earth, the current flows out along the cable and back again. This path is called the fault loop.
  • The longer the cable and the thinner its conductor, the more resistance in the loop and the less current flows in a fault.
  • Protective devices trip fast only above a certain current. If the cable is too long, the fault current can fall below that level and the device trips slowly or not at all.

A worked example

  • Take a copper cable of 4 mm² and 100 m, with a 230 V supply to earth and a 32 A circuit.
  • Loop resistance is about 2 × 0.0225 × 100 ÷ 4 = 1.1 ohms. Fault current is about 230 ÷ 1.1 = 200 A.
  • A breaker of this size may need roughly 160 to 320 A to trip instantly. At 200 A it may trip slowly, so the cable is near the limit.
  • This is an illustration with rounded numbers. Real designs use the supply source resistance, warmer cable resistance, and the maker's tables.

What sets the longest safe length

  • The cable cross-section: thicker conductors allow longer runs.
  • The protective device: its type and its rating.
  • The supply voltage, and the room temperature.
  • The number of cores and how the cable is laid.

A second check: voltage drop

Even when protection works, a long cable drops voltage under load. Motors and electronics need near-rated voltage, so check voltage drop separately from the fault-current check.

If either check fails, use a thicker cable, a shorter route, or a device with a lower trip level.

check yourself

Three quick questions

Think of your answer first, then open the question.

Why does a longer cable reduce fault current?

More loop resistance.

Name two things that decide the longest safe cable length.

For example conductor cross-section and the protective device.

Is the fault-current check the same as the voltage-drop check?

No. Do both.

Learning material, not a design or safety instruction. Electrical work must be done by qualified people following the maker's instructions and local rules.